top of page

What the Revised EU Drinking Water Directive Means for Priority Premises

Nov 13
5 min read

Updated: 6 days ago

The revised EU Drinking Water Directive is the biggest change to European drinking water law in more than twenty years. For the first time, it reaches inside buildings, asking Member States to deal with the risks that arise in the pipework between the water main and the tap. Legionella is at the centre of that change, and the buildings most affected are what the Directive calls priority premises: hospitals, care homes, schools, hotels and other large buildings used by many people.


This guide explains, in plain English, what changed, which buildings are likely to be caught, what a risk assessment of a building's water system involves, and how the rules vary from country to country.


What the revised Directive changed


Directive (EU) 2020/2184 replaced the previous Drinking Water Directive (98/83/EC). Its main shift is a risk-based approach that runs from source to tap, split into three layers:

  1. Catchment areas. Assessing risks around the places where drinking water is abstracted.

  2. Supply systems. Water suppliers assessing and managing risk through treatment, storage and distribution.

  3. Domestic distribution systems. Assessing the risk inside buildings: the pipes, fittings and appliances between the distribution network and the taps.


It is the third layer that matters for building owners and managers. Annex I, Part D of the Directive sets two parameters specifically for this risk assessment: Legionella (below 1,000 CFU per litre) and lead (10 µg per litre). Where Member States find a risk to health from domestic distribution systems, the Directive requires that measures relating to Legionella target, at a minimum, priority premises.

The first risk assessment of domestic distribution systems must be carried out by 12 January 2029, and then reviewed every six years.


What counts as a priority premises


The Directive describes priority premises as large non-household premises with many users who may be exposed to water-related risks. It leaves the detailed list to each Member State, but the types of building it points to include:


  • hospitals and other healthcare facilities

  • care homes and retirement homes

  • schools, childcare facilities and other educational buildings

  • hotels and buildings with overnight accommodation

  • restaurants and bars

  • sports, leisure and recreational facilities

  • prisons

  • campsites


In practice, the definitions vary. Italy, for example, sorts priority buildings into classes under Legislative Decree 18/2023 and includes shopping centres and exhibition venues. In Ireland, the European Union (Drinking Water) Regulations 2023 define priority premises as large non-household premises with many users, identified by the water supplier in consultation with the supervisory authority. If you own or manage one of the building types above, it is safest to assume you are in scope until you have confirmed otherwise.


What a risk assessment of a building's water system involves


For anyone already familiar with workplace legionella risk assessments, much of this will look familiar. A competent assessment of a building's water system will usually cover:


  • Mapping the system. An up-to-date schematic and asset register: incoming supply, storage tanks, water heaters and calorifiers, distribution pipework, outlets, showers and any other equipment that uses water.

  • Identifying hazards. Areas where water stagnates, dead legs, little-used outlets, temperatures in the growth range for Legionella (roughly 20°C to 45°C), poor tank condition, and pipework or fittings that could release lead.

  • Identifying vulnerable users. Patients, elderly residents and young children are more at risk, which shapes how tightly risks need to be controlled.

  • Sampling at the right points. The Directive says Legionella samples should be taken at risk points for proliferation, at points representative of exposure across the system, or both. The reference method is EN ISO 11731.

  • Setting control measures. Temperature control, flushing regimes, cleaning and disinfection, removal of redundant pipework, and any treatment needed.

  • Keeping records. A written record of the assessment, findings, actions and monitoring results, ready for review or inspection.


The aim is not a one-off report. It is a working plan that keeps the system under control between reviews.


How deadlines and duties differ between countries


The 12 January 2029 date comes from the Directive itself, so it applies across the EU. What differs is who is responsible and what they must do, because each Member State has written the Directive into its own law in its own way. A few examples:


  • Finland. Owners of priority premises must carry out a risk assessment of their building's water systems and have control measures in place by 12 January 2029. The national supervisory authority, Valvira, recommends starting as soon as possible.

  • Italy. Managers of priority buildings must complete the first risk assessment by 12 January 2029, enter it on a national system, and review it every six years.

  • Malta. Priority premises must risk assess their domestic distribution system and test for lead as well as Legionella.

  • Ireland. The duty to carry out the general risk assessment of domestic distribution systems sits with Uisce Éireann. Owners of premises supplied with water as part of a commercial or public activity, including priority premises, must keep their internal systems in a condition that does not put water quality at risk.


The practical takeaway is that the date is shared, but the duties are not. If you manage buildings in more than one EU country, each site needs to be checked against that country's own rules.


How this fits with existing workplace legionella duties in Ireland


The new drinking water rules sit alongside Ireland's existing workplace legislation; they do not replace it. Employers already have duties to control legionella under:


In other words, if you run a hotel, care home or school in Ireland, you should already be assessing and controlling legionella risk as an employer. The Drinking Water Regulations add a second, water-quality lens to the same pipework. A well-scoped assessment can address both sets of duties together, rather than treating them as separate exercises with separate paperwork.


Talk to our Europe team about priority premises


January 2029 can feel a long way off, but the time needed to map systems, sample, carry out remedial work and settle into a monitoring routine soon adds up, especially across a portfolio of buildings.

ISHEM's Europe team supports organisations across Ireland and the wider EU. We are independent: we assess and advise, and we do not carry out remediation work, so our recommendations reflect the risk in your building and nothing else. Find out how our Europe team can help you prepare.